2 & 3 Pole Series

Download our full P Spec Sheet

$148.00
More Details
$225.00
More Details
$215.00
More Details

2 & 3 Pole SSRs Quote Form

Quote: Solid State Relays

This product is intended to replace mechanical contactors especially when switching is frequent. The smallest product width in the range is 2.13" (54mm) (3xDIN) and goes up to 2.84" (72 mm).

2-pole and 3-pole switching options are available. Switch ON occurs at the voltage zero cross and switch OFF occurs at the current zero cross. Apart from resistive and slightly inductive loads, the SSR is certified for motor switching with associated motor ratings. Varistors are integrated for output over-voltage protection. A green LED gives indication of control voltage presence. Fan operation is controlled for the versions which have an integrated fan.

Detection of SSR overheat, mains loss, SSR malfunction and load loss is possible with the monitored (-M) versions. An EMR alarm output is available for remote signaling. An additional feature with the monitored (-M) is the electronic auxiliary output. The monitored (-M) has additional LED's for load status and alarm status indication.

Specifications are at a surrounding temperature of 25°C unless otherwise specified.

  • 2-pole & 3-pole AC switching solid state contactors
  • Product width up to 2.84" (72 mm)
  • Rated operational voltage: up to 600 VAC
  • Rated operational current: up to 75 AAC
  • Control voltages: 5-32 VDC, 20-275 VAC (24-190 VDC)
  • Up to 15,000A²s for l²t
  • Motor ratings up to 11 kW @ 400 VAC, 25 HP @ 600 VAC
  • Integrated varistor protection on output
  • Optional monitoring for SSR and load malfunction
  • EMR alarm output and auxiliary output
  • Controlled fan operation for versions with integrated fan
  • UL, cUL Listing
  • 100 kA Short Circuit Current Rating according to UL 508
  • DIN or panel mount
  • RoHS compliant
  • Line & Load accepts: 10-14 AWG (20 & 25 units)
  • Line & Load accepts: 3-14 AWG (30, 40, 65 & 75 units)

Motor Ratings: HP (UL 508) / kW (EN/IEC 60947-4-2) @ 40°C

2PSS60A25
2PSS60D25

115 VAC
1½ HP / 1.1 kW

230 VAC
3 HP / 3.0 kW

400 VAC
5 HP / 5.5 kW

480 VAC
7½ HP / 5.5 kW

600 VAC
10 HP / 9.0 kW

2PSS60A40
2PSS60D40

115 VAC
3 HP / 1.5 kW

230 VAC
5 HP / 4.0 kW

400 VAC
10 HP / 7.5 kW

480 VAC
10 HP / 9.0 kW

600 VAC
15 HP / 11 kW

2PSS60A75
2PSS60D75

115 VAC
5 HP / 3.0 kW

230 VAC
10 HP / 7.5 kW

400 VAC
15 HP / 11 kW

480 VAC
20 HP / 15 kW

600 VAC
25 HP / 22 kW


3PSS60A20
3PSS60D20

115 VAC
1 HP / 0.75 kW

230 VAC
3 HP / 2.2 kW

400 VAC
5 HP / 4.0 kW

480 VAC
7½ HP / 5.5 kW

600 VAC
10 HP / 7.5 kW

3PSS60A25
3PSS60D25

115 VAC
2 HP / 1.1 kW

230 VAC
3 HP / 2.2 kW

400 VAC
7½ HP / 4.0 kW

480 VAC
10 HP / 5.5 kW

600 VAC
10 HP / 7.5 kW

3PSS60A30
3PSS60D30

115 VAC
2 HP / 1.5 kW

230 VAC
5 HP / 3.0 kW

400 VAC
10 HP / 5.5 kW

480 VAC
10 HP / 7.5 kW

600 VAC
15 HP / 11 kW

3PSS60A40
3PSS60D40

115 VAC
2 HP / 1.5 kW

230 VAC
5 HP / 4.0 kW

400 VAC
10 HP / 7.5 kW

480 VAC
10 HP / 9.0 kW

600 VAC
15 HP / 11 kW

3PSS60A65
3PSS60D65

115 VAC
3 HP / 3.0 kW

230 VAC
10 HP / 5.5 kW

400 VAC
15 HP / 11 kW

480 VAC
20 HP / 15 kW

600 VAC
25 HP / 20 kW


Filtering - EN/IEC 55011 Class A Compliance

2PSS60.25
220 nF / 760V / X1
Max. heater AAC 25

2PSS60.40
330 nF / 760V / X1
Max. heater AAC 40

2PSS60.75
470 nF / 760V / X1
Max. heater AAC 65

3PSS60.20
220 nF / 760V / X1
Max. heater AAC 25

3PSS60.25
330 nF / 760V / X1
Max. heater AAC 25

3PSS60.30
470 nF / 760V / X1
Max. heater AAC 30

3PSS60.40
470 nF / 760V / X1
Max. heater AAC 40

3PSS60.65
470 nF / 760V / X1
Max. heater AAC 65


Fusing / Short Circuit Protection

Co-ordinationType 1 (UL508): Suitable For Use On A Circuit Capable Of Delivering Not More Than 100,000 A rms Symmetrical Amperes, 600 Volts Maximum when Protected by Class J Fuses. Use Fuses Only. Tests with Class J fuses are representative of class CC fuses

2PSS60.25
Max. 30A, 600 VAC
Class J or Class CC

2PSS60.40
Max. 40A, 600 VAC Class J
Max. 30A, 600 VAC Class CC

2PSS60.75
Max. 60A, 600 VAC Class J

3PSS60.20
Max. 30A, 600 VAC
Class J or Class CC

3PSS60.25
Max. 30A, 600 VAC
Class J or Class CC

3PSS60.30
Max. 40A, 600 VAC Class J
Max. 30A, 600 VAC Class CC

3PSS60.40
Max. 40A, 600 VAC Class J

3PSS60.65
Max. 60A, 600 VAC Class J


Co-ordination Type 2: Semiconductor fuses, Miniature Circuit Breakers (refer to our P Spec Sheet)

2PSS60.25

Ferraz Shawmut (Mersen)
A70QS40-4

Siba
50 142 06 32

2PSS60.40

Ferraz Shawmut (Mersen)
A70QS60-4

Siba
50 194 20 63

2PSS60.75

Ferraz Shawmut (Mersen)
A70QS100-4

Siba
50 196 20 125

3PSS60.20

Ferraz Shawmut (Mersen)
A70QS40-4

Siba
50 142 06 32

3PSS60.25

Ferraz Shawmut (Mersen)
A70QS40-4

Siba
50 142 06 32

3PSS60.30

Ferraz Shawmut (Mersen)
A70QS40-4

Siba
50 194 20 40

3PSS60.40

Ferraz Shawmut (Mersen)
A70QS50-4

Siba
50 194 20 50

3PSS60.65

Ferraz Shawmut (Mersen)
A70QS100-4

Siba
50 196 20 125